Sensor Indutivo Pepperl Fuchs NJ50-FP-N-P1 NAMUR 50mm

Sensor Indutivo Pepperl Fuchs NJ50-FP-N-P1 NAMUR 50mm

    Preço sob
    consulta

Sensor Indutivo Pepperl Fuchs NJ50-FP-N-P1 NAMUR 50mm


Marca: Pepperl Fuchs


Modelo: NJ50-FP-N-P1


Referência: 106504


General specifications


Switching function Normally closed (NC)

Output type NAMUR

Rated operating distance 50 mm

Installation non-flush

Assured operating distance 0 ... 40.5 mm

Reduction factor rAl 0.4

Reduction factor rCu 0.3

Reduction factor r304 0.85

Output type 2-wire


Nominal ratings


Nominal voltage 8.2 V (Ri approx. 1 kΩ)

Switching frequency 0 ... 100 Hz

Current consumption

Measuring plate not detected ≥ 3 mA

Measuring plate detected ≤ 1 mA


Functional safety related parameters


MTTFd 11400 a

Mission Time (TM) 20 a

Diagnostic Coverage (DC) 0 %


Compliance with standards and directives


Standard conformity

NAMUR EN 60947-5-6:2000

IEC 60947-5-6:1999

Standards EN 60947-5-2:2007

EN 60947-5-2/A1:2012

IEC 60947-5-2:2007

IEC 60947-5-2 AMD 1:2012


Approvals and certificates


IECEx approval

Equipment protection level Ga IECEx PTB 11.0021X

Equipment protection level Gb IECEx PTB 11.0021X

Equipment protection level Da IECEx PTB 11.0021X

Equipment protection level Mb IECEx PTB 11.0021X

ATEX approval

Equipment protection level Ga PTB 00 ATEX 2032 X

Equipment protection level Gb PTB 00 ATEX 2032 X

Equipment protection level Da PTB 00 ATEX 2032 X

UL approval cULus Listed, General Purpose

Ordinary Location E87056

Hazardous Location E501628

Control drawing 116-0451

CCC approval

Hazardous Location 2020322315002304

NEPSI approval

NEPSI certificate GYJ16.1394X

ANZEx 19.3001X


Ambient conditions


Ambient temperature -25 ... 70 °C (-13 ... 158 °F)


Mechanical specifications


Connection type screw terminals

Information for connection A maximum of two conductors with the same core cross section may be mounted on one terminal connection!

tightening torque 1.2 Nm + 10 %

Core cross-section up to 2.5 mm2 , stripped insulation length: 7 mm

Minimum core cross-section without wire end ferrule 0.5 mm2 , with connector sleeves 0.34 mm2

Maximum core cross-section without wire end ferrule 2.5 mm2 , with connector sleeves 1.5 mm2

Connection (system side) screw terminals , M20 x 1.5 cable gland , usable thread length 10 mm , screw-in depth max. 10 mm

Housing material PBT

Sensing face PBT

Degree of protection IP67

Note Tightening torque: 1.8 Nm (housing)


General information


Use in the hazardous area see instruction manuals